GU641B is a new generation Automatic Mains (Utility) Failure module for single Genset, which adopts bran-new outline configuration, focus on the requirements of customers, and perfectly improves the performance of controller. It fully meets the auto control requirements of different kinds of Genset for user or special assembly factory.

The module also monitors and protects the engine, indicating operational status, fault conditions and metering on the front panel LCD and LED.

AC voltage

Measurement True RMS
Phase to Neutral 15 to 346VAC
Phase to Phase 25 to 600VAC
Max power wastage per line <0.1W
Accuracy 1%
Display 0 to 9999V

AC voltage frequency

Input frequency 3 to 70Hz (voltage ≥15VAC)
Accuracy 0.1%
Display 0 to 100Hz

Current (isolated)

Measurement True RMS
Measuring current 5A
Accuracy 1%
Display 0 to 9999A
Max power wastage per line <0.01W

Power supply

Range 12V/24V (8-35V continuous)
Max. operating current @12V 300mA, @24V 150mA
Max. standby current @12V 90mA, @24V 45mA
Cranking dropouts 0V for 80ms, assuming dc supply was at least 10V before dropout and recovers to 5V
Accuracy 1%
Display 0 to 40V
Display 0 to 40V

Configurable digital inputs

Number 5
Max. contact resistance 10KΩ
Type Isolated
Max. contact current per line 1mA

Configurable relay outputs

Fuel relay 16A/30Vdc
Start relay 16A/30Vdc
Aux relay 3A/30Vdc
Max. contact current per line 1mA

Charge failure input

Range 0 to 35Vdc
Accuracy 1%
Max output current @12V 120mA, @24V 240mA

Analog Inputs

Number 2
Sensor type resistance
Resolution 10 bits
Range 0 to 1KΩ
Accuracy 2% When full scale, except for sensor error

Magnetic pickup

Voltage range 1 to 70V
Max. frequency 10000Hz
Fly wheel teeth 5 to 300

Ambient parameters

Operating ambient temperature Standards -20 to 70℃
IEC60068-2-1 and IEC60068-2-2
Storage ambient temperature Standards -30 to 80℃
IEC60068-2-1 and IEC60068-2-2
Humidity Standards 60℃, 95%RH, 48 hours
IEC60068-2-30
Electro Magnetic compatibility (EMC) Standards EN 61000-6-4 and EN 61000-6-2
Vibration Standards EN 60068-2-6
Shock Standards EN 60068-2-27
Electrical safety Standards EN 60950-1
Degrees of protection Standards IP65 (front) IP20 (back)
BS EN 60529
Measurement
2 analog inputs for kinds of optional built-in sensors, parameters also can be configured by user.
More outputs of configurable auxiliary control relays.
More configurable isolated digital inputs.
Buttons on control panel are used for selecting control modes, starting and stopping the operating procedure, displaying data and modifying the parameters. LED indicators are used for indicating the operation mode of controller and the running status of Genset, and LCD displays each measuring parameter and status.
Flexible equipped with RS485, RS232 and USB, realizing remote monitor; or communicated with PC, fully realizing functions of remote signaling, telemetering and remote control, can read and set the running parameters of controller.
All connections of the controller are by secure plug and socket, for ease and convenience to connect, move, maintain and replace the device.