GU641B is a new generation Automatic Mains (Utility) Failure module for single Genset, which adopts
bran-new outline configuration, focus on the requirements of customers, and perfectly improves the
performance of controller. It fully meets the auto control requirements of different kinds of Genset for
user or special assembly factory.
The module also monitors and protects the engine, indicating operational status, fault conditions and
metering on the front panel LCD and LED.
AC voltage
Measurement
|
True RMS
|
Phase to Neutral
|
15 to 346VAC
|
Phase to Phase
|
25 to 600VAC
|
Max power wastage per line
|
<0.1W
|
Accuracy
|
1%
|
Display
|
0 to 9999V
|
AC voltage frequency
Input frequency
|
3 to 70Hz (voltage ≥15VAC)
|
Accuracy
|
0.1%
|
Display
|
0 to 100Hz
|
Current (isolated)
Measurement
|
True RMS
|
Measuring current
|
5A
|
Accuracy
|
1%
|
Display
|
0 to 9999A
|
Max power wastage per line
|
<0.01W
|
Power supply
Range
|
12V/24V (8-35V continuous)
|
Max. operating current
|
@12V 300mA, @24V 150mA
|
Max. standby current
|
@12V 90mA, @24V 45mA
|
Cranking dropouts
|
0V for 80ms, assuming dc supply was at least
10V before dropout and recovers to 5V
|
Accuracy
|
1%
|
Display
|
0 to 40V
|
Display
|
0 to 40V
|
Configurable digital inputs
Number
|
5
|
Max. contact resistance
|
10KΩ
|
Type
|
Isolated
|
Max. contact current per line
|
1mA
|
Configurable relay outputs
Fuel relay
|
16A/30Vdc
|
Start relay
|
16A/30Vdc
|
Aux relay
|
3A/30Vdc
|
Max. contact current per line
|
1mA
|
Charge failure input
Range
|
0 to 35Vdc
|
Accuracy
|
1%
|
Max output current
|
@12V 120mA, @24V 240mA
|
Analog Inputs
Number
|
2
|
Sensor type
|
resistance
|
Resolution
|
10 bits
|
Range
|
0 to 1KΩ
|
Accuracy
|
2% When full scale, except for sensor error
|
Magnetic pickup
Voltage range
|
1 to 70V
|
Max. frequency
|
10000Hz
|
Fly wheel teeth
|
5 to 300
|
Ambient parameters
Operating ambient temperature Standards
|
-20 to 70℃ IEC60068-2-1 and IEC60068-2-2
|
Storage ambient temperature Standards
|
-30 to 80℃ IEC60068-2-1 and IEC60068-2-2
|
Humidity Standards
|
60℃, 95%RH, 48 hours IEC60068-2-30
|
Electro Magnetic compatibility (EMC) Standards
|
EN 61000-6-4 and EN 61000-6-2
|
Vibration Standards
|
EN 60068-2-6
|
Shock Standards
|
EN 60068-2-27
|
Electrical safety Standards
|
EN 60950-1
|
Degrees of protection Standards
|
IP65 (front) IP20 (back) BS EN 60529
|
Measurement
|
2 analog inputs for kinds of optional built-in sensors, parameters also can be configured by user.
|
More outputs of configurable auxiliary control relays.
|
More configurable isolated digital inputs.
|
Buttons on control panel are used for selecting control modes, starting and stopping the operating
procedure, displaying data and modifying the parameters. LED indicators are used for indicating
the operation mode of controller and the running status of Genset, and LCD displays each
measuring parameter and status.
|
Flexible equipped with RS485, RS232 and USB, realizing remote monitor; or communicated with
PC, fully realizing functions of remote signaling, telemetering and remote control, can read and set
the running parameters of controller.
|
All connections of the controller are by secure plug and socket, for ease and convenience to connect,
move, maintain and replace the device.
|